ML-110X Sounder and Beacon
Maxlogic ML-110X Sounder & Beacon
Maxlogic Intelligent addressable loop-powered base sounder is designed for indoor use, in case of ?ire, user is warned by audible and visible warnings. Sounders are microprocessor controlled and outputs can be programmed to work within cause-effect scenarios. Mounting base c/w buzzer, in case of detector alarm, the internal buzzer of mounting base is activated.
◗ Compatible with EN 54-3
◗ Specially designed for indoor use
◗ Loop-powered
◗ 85 dB sound output, 8 tones and volume control
◗ It can be used as a stand alone sounder/sounder beacon
◗ Its primary application is to be installed under intelligent analogue addressable smoke and heat detectors to provide both detection and alarm at the same point, reducing wiring and installation costs
Categories: Fire Alarm, Maxlogic

Description
Maxlogic ML-110X Sounder & Beacon
Maxlogic Intelligent addressable loop-powered base sounder is designed for indoor use, in case of ?ire, user is warned by audible and visible warnings. Sounders are microprocessor controlled and outputs can be programmed to work within cause-effect scenarios. Mounting base c/w buzzer, in case of detector alarm, the internal buzzer of mounting base is activated.◗ Compatible with EN 54-3
◗ Specially designed for indoor use
◗ Loop-powered
◗ 85 dB sound output, 8 tones and volume control
◗ It can be used as a stand alone sounder/sounder beacon
◗ Its primary application is to be installed under intelligent analogue addressable smoke and heat detectors to provide both detection and alarm at the same point, reducing wiring and installation costs

Loop Powered

85 dB sound output, 8 tones and volume control

Mounted

Specially designed for indoor use
About Brand
IOT Hunt is introducing Maxlogic
IOT Hunt is bring Maxlogic to UAE, Saudi Arabia, UK, US, Oman, and Qatar. IOT Hunt are the leading IOT based integrator. We not only introduce IOT solutions but also provide quality products to its customers.

Specifications
Electrical Definitions | ||||||||
Models | ML-1101 | ML-1102 | M-L1103 | |||||
Power Supply Voltage | 18-33V DC Loop powered | |||||||
Quiescent Current (max) | 500 µA | 650 µA | 550 µA | |||||
Alarm current (max) | 3 mA | 10 mA | 9 mA | |||||
Power(max) | 0.10 W | 0.33 W | 0.30 W | |||||
Sound Definitions | ||||||||
Sound intensity at 1m distance | High Sound Intensity: 75 dB(A) | - | ||||||
Low Sound Intensity: 65 dB(A) | - | |||||||
Number of Tones | 8 | - | ||||||
Beacon Definitions | ||||||||
Coverage Volume | - |
|
Open Class; Y: 2.0 m Z: 2.0 m X: 0.45 m | |||||
Flash frequency | - | 0,5 Hz | 0,5 Hz | |||||
LED Color | - | White | White | |||||
Mechanical Definitions | ||||||||
Material | ABS FR Flame Retardant (V0) | |||||||
Dimensions (mm) | 114x32 | |||||||
Weight | 125 gr | 125 gr | 125 gr | |||||
Mounting Type | Ceiling Type (Type A) | |||||||
Body Color | White | |||||||
Cable | 1x2x0.8+0.8JH(st)H / (1x2x1.5+1.5JH(st)H | |||||||
Environmental Definitions | ||||||||
Protection Class | IP21C | |||||||
Operating temperature | (-10°C) - (+55°C) | |||||||
Storage temperature | (-30°C) - (+60°C) | |||||||
Max. relative humidity | %95 (+40°C non-condensing) |
Related products
Manual Call Point Pucar
Cofem Manual Call Point Pucar
Manual call point for the conventional fire detection system. It has an indicator of action (red led) that illuminates in case of be manually operated (alarm). Features: • Resettable call point by pushing yellow button on the front side. • Transparent protector cover to avoid accidental false alarms. • Immediate visual recognition of alarm status by the permanent activation of the LED, and the trigger of • The yellow tab on the lower side of the activation face. • According to EN 54-11 and CE mark according the European Regulation of Construction Products (UE) Nº305/2011.6808 Fire Alarm Control Panel
Honeywell 6808 Addressable Fire Alarm Control Panel
The 198 point addressable fire alarm control panels include connected panel options, enhanced communications, wireless detection, and other advanced features. These panels also support Class B (Style 4) and Class A (Style 6) configuration for SLC, SBUS, and Flexput circuit.ML-051XX SMPS Power Supply
Maxlogic ML-051XX SMPS Power Supply
SPMS power supplies have a stable sensitivity, produced by using surface mount technology and compatible with all Maxlogic & Mavigard series products.◗ Compatible with EN 54-4
◗ In the case of electrical failure, power is supplied from battery, which are automatically recharged.
◗ Automatic battery charge circuit
◗ Battery charge voltage according to ambient temp.
◗ Earth fault, battery fault (charge fault, low voltage fault, no battery connection fault), power and fuse faults are monitored on the power supply unit
◗ Dry contact relay output for faults
◗ In case of electrical failure, supply from battery and protected from short circuit and over current
◗ Battery temperature measurement and automatically arrangement for battery charge voltage